MAGFLO™ Water Temperature Monitoring System
TMV Water Temperature Monitoring System
The MAGFLO™ TMV Water Temperature Monitoring System monitors a building’s water temperature from the TMV outlet, providing a comprehensive risk management tool. It continuously monitors and records temperatures via a calibrated sensor probe, detecting faults that require maintenance. With real-time monitoring, performance updates, and alarms for any temperature deviations, the system ensures the safety and compliance of all TMVs throughout the facility. Our customised solution includes all wiring, electrical components, programming, and comes fully commissioned, ready to use. The sensor probes are installed on the outlet pipework of the TMVs for continuous monitoring. The water outlet setpoint of the TMV is generally 43.5°C. Can be connected to/integrate with existing BACnet® Building Automation Systems.
Features and Benefits of TMV Water Temperature Monitoring System
- Real time monitoring of water temperature
- Multi monitoring of temperature from all TMVs
- Real time reporting, including logging of all temperatures – allows ability to respond promptly to any problems
- Building Management Integration – can be connected to, and integrates with, existing BACnet® Building Automation Systems
- Live updating on display screens
- Reduced maintenance costs, procedures and less downtime
- Efficient facility management (streamlined monitoring and identification of problems, effective reporting)
- Out of temperature range alarming 24/7
- Flexible and secure access to different groups of users
- No mixing chamber required – ideal with FM Mattsson TMVs
- Easy to install and use
- The monitoring sensors are connected to enteliBUS Manager (eBMGR), a fully programmable native BACnet® Building Controller
Features and Benefits of enteliBUS Manager (eBMGR)
- Fully programmable, the Manager also provides the control logic for enteliBUS I/O expansion backplanes
- User experience can be tailored to meet specific needs
- For control at a finger’s touch and communication with remote networks
- Standard high-resolution color display and customizable screens provide an easy-to-use graphical interface tailored to your needs
- Advanced fault detection and diagnostics
- LED status indications of power, CPU Scan and Ethernet ports
- Small footprint
- Modular design for flexibility, ease of service and reduced cost for future expansion
General Information
- Stable industrial RS485 Standard Communications
- IP65 rated at sensor and buffer end
- Intervals from 10 seconds to 1 day
- Readings in degrees C or F
- Save files to your directory/Back up HDD
- Unique ID number per point
- Provides both audible and visual alarms (i.e., sensor ‘fail’ status and ‘out of range’ status)
- Can also email critical alarms if required
How It Works
The enteliBUS Manager supports multiple communications methods including, as standard, BACnet/IP, BACnet over Ethernet, BACnet MS/TP (Master Slave/Token Passing), and Delta LINKnet. The Manager is the automation engine of the enteliBUS Control System. It contains the primary CPU, memory storage and external communication ports. The TMV Water Temperature Monitoring System constantly monitors the valves outlet temperature electronically, through a calibrated sensor probe installed into the outlet pipework of the TMV. This provides real time monitoring of water temperature, performance status of all TMVs throughout the facility, live updating on display screens and provides a warning via an alarm if an out-of-temperature event is detected.
Temperature Logging and Reporting
- Real time temperature readings of the TMVs are logged once per minute (adjustable) within the system server which resides locally on site for full control and real-time access
- Professional, built in reports can be generated for all TMV’S monitored from a report wizard or saved in a library
- The reporting system is flexible and delivers custom reports which can be emailed automatically to a schedule (e.g., daily, weekly, etc).
- Output options include PDF, CSV and web.
- Data can be presented in enterprise, personal or system dashboards to meet your exact needs
- Dashboards and object pages can also be optimized for viewing on your smartphone or tablet
Temperature Alarm
Each TMV is monitored for three separate alarm conditions:
- High Temperature Alarm – will activate when the temperature rises above the high temperature set point of 48°C (adjustable). The alarm condition will return to normal upon the temperature falling below the high temperature setpoint.
- Low Temperature Alarm – will activate when the temperature falls below the low temperature set point of 38°C (adjustable) for over 24 Hours (adjustable). The alarm condition will return to normal upon the temperature rising above the low temperature set point.
- Sensor Fault Alarm – will activate upon the system monitoring a pre-set high and low limit of each temperature probe. Any TMV outside of these parameters will generate a sensor faulty condition alarm. The alarm condition will return to normal upon the probe reading within the pre-set parameters.
Applications:
Hospitals and healthcare facilities, Aged care centres, Schools and universities, Commercial buildings, Government buildings, Hotels and hospitality, Correctional facilities, Sports and aquatic centres, Any site requiring TMV compliance logging
- Installation should comply to AS3500 - National Australian Plumbing Code and any other local and applicable codes
- Image is for illustration purposes only
- Due to continuous product improvement, changes to specifications may be made without prior notice