Tepid Water System for Emergency Showers and Eye Wash – Pre-Plumbed in a Box
MAG5193EEFWU/CAB
The heart of the Tepid Water System for Emergency Showers and Eye Wash MAG5193EEFWU/CAB is FM Mattsson “High Flow” Pressure Balanced TMV. This valve features a unique pressure balanced piston design that guarantees stable and safe water temperatures, even when there are fluctuations in pipework pressure (NO pressure reducing valves required) It is WaterMark approved to AS 4032.1 standard and specifically engineered for workforce safety in emergency eyewash stations and showers, ensuring compliance with both AS4775 – Emergency Eyewash and Shower Equipment, and ANSI Z 358.1 standards. When paired with a certified eyewash or eye/face wash system, the assembly provides a consistent warm water flow of 75L/minute (at 300 kPa), ensuring reliable operation during emergencies. In the event of hot water failure, the system’s cold water bypass activates automatically, maintaining an uninterrupted water supply and preserving the full functionality of the emergency shower. This ensures continuous compliance with safety regulations.
Features and Benefits – Tepid Water System
- Cold water bypass ensures continued cold water flow during hot water supply failure
- ANSI Z 358.1 Compliant
- AS 4775 Compliant
- WaterMark-approved to AS 4032.1 standards
- Delivers water within a temperature range of 15.6°C to 37.8°C with a minimum flow rate of 11.4L/min
- Maximum flow rate 97.5 L/min at 500 kPa inlet pressure
- Ensures an uninterrupted flow of 75L/min at 300 kPa inlet pressure
- Includes a FM Mattsson BTMV – Low Flow-High Flow 5193-8070
- Fixed temperature knob to prevent unauthorised interference
- Handles pressure differentials up to 13:1, without a pressure-reducing valves
- Also available in a pre-plumbed box
Features and Benefits of 5193-8070
- Pre-plumbed with 25mm pipework in and out
- Comes with check valves and line strainers built into the isolating valves supplied with the valve
- Maximum flow rate of 97.5L per minute
- With three regulation cartridges to cater for high flow rates – each of the three cartridges have thermostatic temperature control and pressure balancing control in the simple cartridge design
- Maintains constant temperature and pressure in all low flow and high flow situations
Features and Benefits of FM Mattsson PBTMV
- Thermal flush capability
- Inbuilt non return valves and filters
- Factory pre-set to 38°C (can be re-calibrated by licensed plumber)
- Maintain a consistent mixed water temperature within ±1°C no matter what happens in the pipework
- The pressure-balancing system ensures safety and stability even with unequal supply pressures (up to a 13:1 ratio)
- Operates with a minimum flow rate of 1L/minute
- Pressure-limiting valves not required
- Suitable for multi and single point installations
- Fixed temperature knob to prevent unauthorised access
- 5-year warranty on the cartridge (*T&C Apply)
- PBTMV Made in Sweden
- Also available mounted on a plate fully Australian Made
Operating Parameters of FM Mattsson PBTMV
- Operating Outlet Temperature Range: the valve maintains water temperature in the range of 20°C to 50°C
- Unit must have flow control devices fitted between it and each outlet
- Operates from 50kPa to 1000kPa
- Recommended working pressure 100kPa to 500kPa
- Cold and Hot Water Temperature Inlets:
- Cold water supply: Minimum 5°C
- Hot water supply: Maximum 85°C
Thermal Flush Legionella Control
- Only authorised staff and licensed or registered plumbing practitioners are to conduct thermal flush disinfect mode to prevent scalding during the process
- Ensure all outlets to be flushed are unoccupied during the process
- Ensure full compliance in accordance with all relevant and applicable codes and standards
- Thermal Flush for Legionella control – simply remove the Red Lock-shield cap, wind out the valve completely to flush through the desired / maximum degree of hot water
Suitable application for the PBTMV 5193-8070
- Health, aged care facilities and special needs (e.g.: hospitals, nursing homes, senior living, safety showers and eyewash units, disabled bathrooms)
- Public buildings (e.g.: airports, stations, community facilities, public baths, hydrotherapy pools, aquatic and recreational centres)
- Institutional buildings (e.g.: child care facilities, schools, police stations, correctional and prison buildings, work end-of-trip facilities, gymnasiums and sport facilities)
- Commercial buildings (e.g.: hotels, shopping centres)
- Industrial building (e.g.: meat/food processing facilities)
- Installation should comply to AS3500 - National Australian Plumbing Code and any other local and applicable codes
- Image is for illustration purposes only
- Due to continuous product improvement, changes to specifications may be made without prior notice