Drain Tempering Valve (DTV)
- 325/15 – 15mm DTV
- 326/20 – 20mm DTV
- 237/25 – 25mm DTV
The Drain Tempering Valve or DTV is a self-operating, temperature actuated valve designed to respond to elevated drain temperature and allow cold water to flow into the drain to keep the drain effluent below the maximum allowable temperature. Since the DTV is open only when the effluent exceeds the specified set-point temperature, it conserves water by automatically turning off cold water when not needed.
Features and Benefits
- Exclusive Thermoloid® thermal actuator
- Rugged, clog-resistant valve design
- Modulates to conserve cooling water
- Effluent tempering capacity limited only by cold water flow rate through DTV
- Prevents damage to PVC piping due to over-temperature conditions
- Self-operating, no power or signal required
- Minimises water waste
- Easy to install
- Adaptable to almost any drain size
Product Info
- Install using standard pipe fittings and tools
- Maximum Inlet Pressure – 875kPa
- Maximum Temperature – 121°C
- Closing temperature is typically -12°C below opening temperature
- Compliant with drain temperature limitations of plumbing codes
Applications
The DTV can be used in applications where a high temperature discharge flow to a drain/sewer must be tempered with cold water, i.e.:
- Humidifier discharge to sewer/drain
- Commercial Dishwashers
- Boiler blowdown drain lines
- Autoclave Discharge
- Any excessively hot effluent flow to the sewer/drain
Operations
The DTV is installed into the drain line such that the hot effluent passes over the thermal actuator of the DTV and this thermal actuator controls the cold water inlet port. If the hot effluent is above the specified set-point, the DTV opens to allow injection of cold water. As the hot effluent cools, the DTV automatically modulates to reduce the cold water inlet flow. At -12°C below the full open temperature, the cold water inlet is fully closed to conserve water.
- Installation should comply to AS3500 - National Australian Plumbing Code and any other local and applicable codes
- Image is for illustration purposes only
- Due to continuous product improvement, changes to specifications may be made without prior notice