Sensa-Flush™ Urinal Flushing System
Product Code
- 96005/SM – Sensa-Flush™ Single Urinal Sensor
- 96005/DM – Sensa-Flush™ Double Urinal Sensor
- 96005KIT – Sensa-Flush™ Urinal Installation Kit
Spare Parts
- 91189 – Single Microwave Sensor
- 91190 – Double Microwave Sensor
Product Overview
Sensa-Flush™ Urinal Flushing System is compatible with all urinal types, including wall and stalls urinals. The hands-free sensor-operated flush system is designed to reliably flushes the urinal after each user without over flushing. Its compact, modular construction means it has the flexibility to be installed quickly and easily into almost any building configuration.
Features and Benefits
- Hands-free sensor-operated flush system – designed to enhance hygiene and convenience, reliably flushes the urinal after each user
- Compatible with all urinal types, including wall and stall urinals
- Compact and modular construction – easy integration into various building configurations
- Simple integration into new or existing urinal systems
- Hidden, vandal-proof sensor – advanced in-wall / in-ceiling installation
- Operates through plasterboard and other low-density materials
- Adjustable sensing range up to 3.0m in depth and 2.5m in width
- Detects user movement and triggers a flush after a 60secs delay
- Ignores subsequent movement for 20secs to prevent excess water use
- System runs from a power point via a low-voltage power pack – no battery maintenance needed
- Adjustable flush volume
- WELS 5 Star rating based on average flush of 0.91L
- Designed and manufactured in Australia
Product Specifications
- Supply Voltage: 240 VAC to plug pack (supplied); 24 VAC to the unit and actuator
- Power Consumption: 9 watts maximum at flush
- Sensor Type: Very low power, microwave movement sensor
- Sensor Location: Ceiling space or wall cavity
- Sensing Range:
- Adjustable, tear drop shaped:
- 0.7 to 3.0 metres in depth
- 0.5 to 2.5 metres in width.
- Varies due to the nature of the microwave sensor, and the building’s construction
- Adjustable, tear drop shaped:
- Sensor Penetration: Unit can detect users through plaster, timber, light masonry, etc – Some thicker materials may reduce sensor range
- Urinal Types: Large multi-user slab to individual or multi plumbed, wall hung units
- Flush Volume: 0.91L (adjustable), depending on actuator, timing and regulatory requirements
- Special Applications: Can be developed to meet your requirements
Operation
- The movement of a user at the urinal is detected by the sensor and control box (usually mounted above the ceiling board or behind the wall board, over the urinal to be flushed)
- After a 60 second delay, the urinal is flushed by the actuator
- Immediately after flushing, the presence of users is ignored for about 20 seconds to prevent excessive water consumption
- The sensor then reactivates, waiting for a user
- If the urinal is in continuous use by any number of users, flushing takes place every 60 seconds
- If a user is not present, flushing ceases until a user is once again detected. Programmed flushing can also be provided if required
Installation Kit Includes
- Solenoid
- Air Break
- Isolating Valve
Sensa-Flush™ Sectional View
Slab Type Urinal with 3 Inlet Sparges Configuration Example
Single Wall-Hung Urinal Configuration Example
Six Wall-Hung Urinals Configuration Example
Note:
- Installation should comply to AS3500 - National Australian Plumbing Code and any other local and applicable codes
- Image is for illustration purposes only
- Due to continuous product improvement, changes to specifications may be made without prior notice