Pre-Plumbed Horne In-Line Thermal Disinfection Unit (ILTDU)
Product Code
42501
Product Overview
42501 – In-line Thermal Disinfection Unit (ILTDU) in a recessed pre-plumbed box with a lockable hinged lid and pipes at both ends. The ILTDU facilitates periodic high temperature thermal disinfection using the readily available hot water supply. The thermal regime can be extended to the point of water discharge: therefore, the wetted surfaces of all downstream components, i.e., taps, and showers are safely flushed.
Features and Benefits of Pre-Plumbed Horne ILTDU – 42501
- Proudly Made in Australia
- Can be pre-plumbed with or without a TMV
- Servicing is easy and accessible from the front of the box
- All the features and benefits of Horne ILTDU
Features and Benefits of Horne ILTDU
- The disinfection mode is activated by turning the unique key
- Enables periodic high-temperature thermal disinfection using the existing hot water supply, raising downstream components to system temperature ensuring downstream fittings are safely flushed
- Designed to combat bacterial contamination such as Legionella and Pseudomonas
- Prevents biofilm growth in “dead-leg” or low-flow pipework, improving hygiene in domestic and commercial hot water systems
- Durable chrome-plated valve body designed for long service life
- Engineered for accurate and stable temperature control
- Horne ILTDU compact in-line design integrates easily into an existing pipework, and can be pre-plumbed with or without a TMV
- Compatible with existing plumbing layouts
- Ideal for hospitals, aged care, correctional, educational, and sporting facilities
- WaterMark approved: WMK26181
If you would like to have different piping configurations for your pre-plumbed boxes, please Contact Us
Product Specifications
- Dimensions: 260mm (W) x 300mm (H) x 75mm (D)
- Water Connection: 3/4″ BSP
Technical Specs (ILTDU)
- Body: DZR brass
- Seals: Nitrile/PTFE
- Four way link mechanism: stainless steel
- Pipe Connections: compression fitting 15mm
- Measurement: 51 mm between pipe centres
- Weight: 1.0kg
- Max working pressure (static): 1000kPa
- Max temperature: 85°C
How It Works
- When not in use (Passive Mode), hot and cold water flows to the mixing valve and downstream fittings uninterrupted
- The operation key transfers the mechanism into Disinfection Mode; diverting hot water at system temperature to the cold water supply pipe drop
- Simultaneously, the cold water supply is closed
- Hot water at system temperature is now able to permeate all wetted parts of the system downstream of the ILTDU until the key is turned back to the passive position
- The ILTDU is operated using a unique key, which has a large red warning notice indicating the hazard of scalding hot water
- Thermal disinfection of outlets should be conducted by an appointed Responsible Person
- During disinfection, it is not possible to remove the key from the device – ensuring the warning notice is visible throughout the process
- Only on returning the device to Passive Mode will the key be removable, an immediate removal of the key following disinfection is good practice
- A local risk assessment should be conducted to ascertain the temperature and duration required for effective thermal disinfection
- For maximum effectiveness in improving water quality and minimising the rate of contamination, thermal disinfection should be conducted in combination (but not simultaneously) with elevated velocity flushing via the drain points of any downstream thermostatic mixing valve
Applications
Ideal for hospitals, aged care, and commercial facilities requiring stringent water hygiene management